Temperature & humidity sensors in each zone — need to confirm on planning layout.

Door width of Investigational Drug Storage Room
Door width must be 40” wide plus to accommodate refrigerator electrical box and door handles in its installed state. Need confirmation in writing or drawing. Otherwise, install a double door.

Door swings outward in Investigational Drug Storage Room

Need to see window product description/spec design for Medication Room.

Venturi Valve relocated inside room just above bio-safety hoods in Hazardous General Workroom


Build abarrier wall in the plenum space above the Hazardous Workroom, 4202E, for infection control

Need back of hood and wall to have 10 inch clearance depicted in planning layout


Pass box install flushed with wall in the Hazardous Workroom & Non-Hazardous Workroom

Pass box door clearance 35” above ground in Hazardous & Non-Hazardous Workroom

Dynamic pass-through box in the Hazardous Workroom & Non-Hazardous Workroom
Dynamic pass-through chambers and vented pass-through chambers each have their advantages, and the choice between them depends on the specific needs and requirements of the cleanroom environment. A dynamic pass-through chamber might be preferred in the following circumstances:
- High Contamination Risk: If the materials being transferred have a high risk of bringing contamination into the cleanroom, a dynamic pass-through chamber with its active decontamination system (like an air shower or UV light) could be more effective at removing or neutralizing these contaminants.
- High Sterility Requirements: In environments that require extremely high levels of sterility, such as those in certain pharmaceutical or biotech applications, the active decontamination provided by a dynamic pass-through chamber can be beneficial.
Install flat grille plate covers in all low wall returns Hazardous (4202E), Ante (4202F), and Non-Hazardous Workroom (4202G)
Line of Demarcation at entrance in the Hazardous Workroom

Data outlets & Switch for Hazardous Workroom

Sink faucet mounted on side, not top, in the Ante Room
Line of Demarcation in the Ante Room and Bench mount

Electrical outlet in the Ante Room

Data outlets, electrical & Switch for Non-Hazardous Workroom

Data outlets and electrical in the Receiving Area and Haz. Drug Storage

Data outlets & electrical in the Tech General Workstation

Data outlet & Dedicated 15-amp outlet for Investigational Drug Storage Room

Data outlets and electrical in the Clinical Trials Workstation

Data outlets in the Corridor Workstation (bottom)
Need 3 ethernet ports for Zebra printer, IDS printer, and phone/PC
Need quad electrical outlet for printers and PC/scanner

Data outlets in the Corridor Workstation (top)

Data outlets and electrical in the Pharmacist Office

Substitute wall panels in corridor with slanted shelf units

Substitute some lockers in the corridor for a metal cabinet

Room description and number corrections on floor plan